Optimization of Lead Insulations for HVDC Converter Transformers

  • Yea, Manje
  • Park, Jaeyong
  • Lee, Seungwook
  • Choi, Jongung
  • Han, Ki Jin
Citations

WEB OF SCIENCE

1
Citations

SCOPUS

4

초록

This paper explains design considerations for lead and lead-exit insulations of HVDC converter transformer for the purpose of automated design optimization. A HVDC converter transformer should at least deal with AC, DC, and DC polarity reversal stresses, which complicate designing process of insulation structures. Design considerations for those insulations are the types of electrical stresses and design parameters of insulation shapes. The design objective of the optimization is to ensure insulation robustness with reduced size of insulation structures. Optimization results showed 16.72% and 29.07% of length reduction with sufficient robustness, for lead and lead-exit insulations, respectively.

키워드

Design optimizationHVDCTransformerInsulationLeadLead-exit
제목
Optimization of Lead Insulations for HVDC Converter Transformers
저자
Yea, ManjePark, JaeyongLee, SeungwookChoi, JongungHan, Ki Jin
DOI
10.1007/s42835-019-00195-w
발행일
2019-09
유형
Article
저널명
Journal of Electrical Engineering & Technology
14
5
페이지
2057 ~ 2063