Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

마찰 슬라이딩 거동을 보이는 건물 내 중량 설비의 내진성능 향상을 위한 감쇠기 연결 방안

Full metadata record
DC Field Value Language
dc.contributor.author옥승용-
dc.contributor.author박관순-
dc.contributor.author이지호-
dc.date.accessioned2023-04-28T00:40:46Z-
dc.date.available2023-04-28T00:40:46Z-
dc.date.issued2020-02-
dc.identifier.issn1738-3803-
dc.identifier.issn2383-9953-
dc.identifier.urihttps://scholarworks.dongguk.edu/handle/sw.dongguk/6940-
dc.description.abstractThis study proposes a new damper configuration for seismic performance improvement of heavy sliding facilities inside a building. For this purpose, we deal with two connection types of control system, and the parametric study has been performed to investigate their comparative seismic performances according to the variations of the control capacity. In order to simulate the seismic responses of the proposed system, we employed a recently-developed seismic response analysis method that can deal with the two-mass system with nonlinear frictional sliding behavior. The numerical results demonstrate that the typical method of diagonal bracing damper connection can exhibit effective control performance both on structure and the heavy sliding facilities, whereas the structure-facilities connection method does not show any control effect on both responses. On the other hand, the typical method has some limitations that it can adversely cause excessive sliding of the facilities, depending upon the frequency characteristics of structure and earthquake. On the contrary, the structure-facilities connection method is very effective in reducing the sliding displacement of the heavy facilities, even with small amount of control capacity. Thus, the following potential expectations can be inferred from these results: The typical diagonal bracing damper connection method will have some promising benefits in controlling the sliding facilities inside the building as well as the building itself, and the structure-facilities connection method can be a cost-effective way of protecting the internal heavy important facilities inside the structure already designed with sufficient seismic performance.-
dc.format.extent9-
dc.language한국어-
dc.language.isoKOR-
dc.publisher한국안전학회-
dc.title마찰 슬라이딩 거동을 보이는 건물 내 중량 설비의 내진성능 향상을 위한 감쇠기 연결 방안-
dc.title.alternativeDamper Configuration for Seismic Performance Improvement of Heavy Facilities with Frictional Sliding Behavior inside Building-
dc.typeArticle-
dc.publisher.location대한민국-
dc.identifier.doi10.14346/JKOSOS.2020.35.1.53-
dc.identifier.bibliographicCitation한국안전학회지, v.35, no.1, pp 53 - 61-
dc.citation.title한국안전학회지-
dc.citation.volume35-
dc.citation.number1-
dc.citation.startPage53-
dc.citation.endPage61-
dc.identifier.kciidART002563910-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorseismic reinforcement-
dc.subject.keywordAuthorsecondary system-
dc.subject.keywordAuthorfrictional sliding behavior-
dc.subject.keywordAuthornonlinear response analysis-
dc.subject.keywordAuthorpassive viscous damper-
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Civil and Environmental Engineering > 1. Journal Articles
College of Engineering > Department of Architectural Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Jee Ho photo

Lee, Jee Ho
College of Engineering (Department of Civil and Environmental Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE