Cited 5 time in
Design and Stability Analysis of a Fuzzy Adaptive SMC System for Three-Phase UPS Inverter
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Naheem, Khawar | - |
| dc.contributor.author | Choi, Young-Sik | - |
| dc.contributor.author | Mwasilu, Francis | - |
| dc.contributor.author | Choi, Han Ho | - |
| dc.contributor.author | Jung, Jin-Woo | - |
| dc.date.accessioned | 2024-08-08T07:30:45Z | - |
| dc.date.available | 2024-08-08T07:30:45Z | - |
| dc.date.issued | 2014-07 | - |
| dc.identifier.issn | 1598-2092 | - |
| dc.identifier.issn | 2093-4718 | - |
| dc.identifier.uri | https://scholarworks.dongguk.edu/handle/sw.dongguk/19527 | - |
| dc.description.abstract | This paper proposes a combined fuzzy adaptive sliding-mode voltage controller (FASVC) for a three-phase UPS inverter. The proposed FASVC encapsulates two control terms: a fuzzy adaptive compensation control term, which solves the problem of parameter uncertainties, and a sliding-mode feedback control term, which stabilizes the error dynamics of the system. To extract precise load current information, the proposed method uses a conventional load current observer instead of current sensors. In addition, the stability of the proposed control scheme is fully guaranteed by using the Lyapunov stability theory. It is shown that the proposed FASVC can attain excellent voltage regulation features such as a fast dynamic response, low total harmonic distortion (THD), and a small steady-state error under sudden load disturbances, nonlinear loads, and unbalanced loads in the existence of the parameter uncertainties. Finally, experimental results are obtained from a prototype 1 kVA three-phase UPS inverter system via a TMS320F28335 DSP. A comparison of these results with those obtained from a conventional sliding-mode controller (SMC) confirms the superior transient and steady-state performances of the proposed control technique. | - |
| dc.format.extent | 8 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.publisher | KOREAN INST POWER ELECTRONICS | - |
| dc.title | Design and Stability Analysis of a Fuzzy Adaptive SMC System for Three-Phase UPS Inverter | - |
| dc.type | Article | - |
| dc.publisher.location | 대한민국 | - |
| dc.identifier.doi | 10.6113/JPE.2014.14.4.704 | - |
| dc.identifier.scopusid | 2-s2.0-84904676108 | - |
| dc.identifier.wosid | 000339132600010 | - |
| dc.identifier.bibliographicCitation | JOURNAL OF POWER ELECTRONICS, v.14, no.4, pp 704 - 711 | - |
| dc.citation.title | JOURNAL OF POWER ELECTRONICS | - |
| dc.citation.volume | 14 | - |
| dc.citation.number | 4 | - |
| dc.citation.startPage | 704 | - |
| dc.citation.endPage | 711 | - |
| dc.type.docType | Article | - |
| dc.identifier.kciid | ART001896226 | - |
| dc.description.isOpenAccess | Y | - |
| dc.description.journalRegisteredClass | scie | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.description.journalRegisteredClass | kci | - |
| dc.relation.journalResearchArea | Engineering | - |
| dc.relation.journalWebOfScienceCategory | Engineering, Electrical & Electronic | - |
| dc.subject.keywordPlus | HARMONIC CURRENT COMPENSATION | - |
| dc.subject.keywordPlus | SLIDING-MODE CONTROL | - |
| dc.subject.keywordPlus | CONTROLLER | - |
| dc.subject.keywordPlus | FILTER | - |
| dc.subject.keywordAuthor | Fuzzy Adaptive Sliding-mode Voltage Controller (FASVC) | - |
| dc.subject.keywordAuthor | Three-phase inverter | - |
| dc.subject.keywordAuthor | Total Harmonic Distortion (THD) | - |
| dc.subject.keywordAuthor | Uninterruptible Power Supply (UPS) | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
30, Pildong-ro 1-gil, Jung-gu, Seoul, 04620, Republic of Korea+82-2-2260-3114
Copyright(c) 2023 DONGGUK UNIVERSITY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.